Professional digital groundmeter and specific resistance of the earth GEO416 GEO416 measures the ground resistance on the 2nd or the 3rd to wire diagram with the minimum permission 0,01 Ohm and the specific resistance Of rho earth on the 4th to wire diagram with the minimum permission 0,01 Ohm x m.
Instrument is allowed:
- To conduct the measurement of the ground resistance according to 2 or 3 wire diagrams
- High range of measurements (50kOhm)
- Automatic [kalibratsiya] on the measured cable
- It reflects the interferences of the stress
- Aid on the display reflects
- To produce the calculations of the results of the measurements
- To conduct the measurement of the specific resistance of the earth according to 4 wire diagrams
- To memorize the results
Instrument can preserve test results beside the memory and transfer information on PK with the aid of [opticheskogo]/USB of cable; also it has the built-in interface RS232 and large [ZHKD]. Performance of instrument with the dual isolation of housing (class 2). Nourishment from the small batteries or the network through the adapter.
Specification
|
Measurement of the ground resistance according to 2 and 3 diagrams |
|
Range RE, W |
Permission, W |
Accuracy |
|
0,01 - 19,99 |
0,01 |
± 2,5%[IV] + of 2 unit of mf |
|
20,0 - 199,9 |
0,1 |
|
200 - 1999 |
1 |
|
2.00 - 19.99k |
0.01k |
|
20.0 - 49.9k |
0.1k |
|
Test signal 75 Hz ± of 1 Hz Test current/stress to 12 mA/to 25[V] Test of resistance to 50 kW |
|
Measurement of the ground resistance according to 4 diagrams |
|
Range R, W[m] |
Permission, W[m] |
Accuracy |
|
0,06 - 19,99 |
0,01 |
± 2,5%[IV] + of 2 unit of mf |
|
20,0 - 199,9 |
0,1 |
|
200 - 1999 |
1 |
|
2,00 - 19,99 k |
0.01 k |
|
20.0 - 199.9 k |
0.1 k |
|
0.20 - 3.15 m |
0.01 m |
|
Test signal 77.5 Hz ± of 1 Hz Test current/stress to 12 mA/to 25[V] Test of resistance to 50 kW Distance of | |