the bodies: (812) 324-56-27, e-mail:
The main thing is the order of catalog the certification of the news To c[tat] by dealer the order of instrument contacts all goods the instruments
1 [u].[e]. = of 1 USD before the rubles on the course TsB RF on the day of payment.    
Search
Basket
Catalog
Multifunctional tester Of speedTest 2018

SpeedTest 2018 makes it possible to define BONDS general (A, ACE) and selective type parameters both before the automatic and before the manual regime. It can measure the impedance of grounding without turning off OF BONDS, measure the impedance of chain “phase- phase”, “phase - neutral particle”, “phase - the earth” and calculate the value of the expected current [KZ], and also determine phase sequence. You can memorize the results of testing before the memory of instrument, transfer them beside the computer for further the processing.

Instrument makes it possible to carry out

  • Measurement of the parameters OF BONDS (ACE, common and selective type a) - tripping time, the current of turning off, contact voltage, the impedance of the ground circuit
  • The measurement of the impedance of chain “phase- phase”, “phase is the earth” and “phase - neutral particle”, the calculation of the expected short-circuit current
  • Determination of phase sequence
  • Record of results, the built-in interface RS232

Specification

Checking the tripping time OF THE BONDS
Test current: 10/30100/300/500 mA
Type OF THE BONDS: ACE, A general and selective
Stress is phase/the earth: 100 - 255[V], 50 Hz

Range, ms

Permission, ms

Accuracy

½ IΔN, IΔN0 - 999

2IΔN0 - 200 general

0 - 250 selective

5IΔN[UZO] is 0 - is 50 is general

0 - 160 selective

1

±2%[IV] of +2 unit of mf

Contact voltage Of u[p]

Stress, before

Permission, before

Accuracy

0 - 2 * U[p] (U[p] from 25 [v] to 50 c)

0,1

-0%, + 2%[IV] of +2 unit of mf

Measurement of the impedance of grounding without turning off OF THE BONDS

Range, W

Permission, W

Accuracy IΔN

1 1999

1

-0%, + 2%[IV] of +2 unit of mf

Test current 0,5 IDN for the test Of u[p], 15[mA] for Ra of 15[mA] test

Checking the differential current of turning off OF THE BONDS

Type OF THE BONDS

Range IDN, mA

Permission, mA

Accuracy IDN

With IΔN of ≤ 10 mA

ACE

(0,5 - 1,4) *IΔN

0,1*IΔN

-0%, + 5% OF IΔN

A

(0,5 - 2,4) *IΔN

0,1*IΔN

-0%, + 5% OF IΔN

With IΔN of >10 mA

ACE

(0,5 - 1,4) *IΔN

0,1*IΔN

-0%, + 5% OF IΔN

A

(0,5 - 2)*IΔN

0,1*IΔN

-0%, + 5% OF IΔN

Frequency (current loop and measurement BY BONDS actively only with 50[Gts])

Range, Hz

Permission, Hz

Accuracy

15,3 - 99,9

0,1

±0,1%[IV] of +1 unit of mf

Stress

Type of the network

Range, before

Permission

Accuracy

Single-phase

0-250

1

±2% of IV of +2 unit of mf

2 or 3 phase

0 - 440

1

±5% of IV of +2 unit of mf

Measurement of the resistance of chain (phase- phase, phase - neutral particle)

Range, W

Permission, W

Accuracy

0,01 - 19,99

0,01

±5% of IV of +3 unit of mf

20,0 - 199,9

0,1

Max. current spikes with the test stress: 100[V] of 3,17[A]
                                                                                   230[V] of 6,64[A]
                                                                                   400[V] of 11,5[A]
the accuracy of the measurement of the current ± 10% Imax Pk
frequency test 50[Gts]

The measurement of the resistance of tire (phase - earth)

Range, W

Permission, W

Accuracy

0,01 - 19,99

0,01

±5% of IV of +2 unit of mf

20,0 - 199,9

0,1

200 - 1999

1

Max. current spikes with the test stress: 100[V] of 3,17[A] the duration of test 80 ms

230[V] of 6,64[A] the duration of test 40 ms

the accuracy of the measurement of the current ± 10% Imax Pk

frequency test 50[Gts]

The measurement of the resistance of tire without turning off BONDS (phase - earth) Ra of 15[mA]

Range, W

Permission, W

Accuracy

1 1999

1

±5% of IV + of 2 unit of mf

Test current 15 mA

Test frequency of 50[Gts]

Delivery set
C2033 - 3 wire cable adapter - the plug
BORSA2000 - case
Management of the user
Certificate of calibration on ISO9000,
Guarantee certificate,
Form of the service maintenance

Options
UNIVERSALKIT - 3 “crocodile”, 3 cables





Current page: Multifunctional tester for determining the parameters OF BONDS and resistance of the ground Of speedtest 2018
Multifunctional tester for determining the parameters OF BONDS and resistance of the ground Of speedtest 2018
Home Sitemap Contact us

Most powerful site:
häusliche Betreuung , hafta hafta hamilelik , Holzhaus , autos.money4car.co.uk , Car credit , Used auto reviews