Testing power stations and substations, networks
- Analysis of the quality of the electric power
- Measurement and the analysis of environmental parameters
But also
-
Checking the electric brushes of industrial objects according to standards CEI 64-8, EN61557, VDE 0100, BS 7661
-
Checking integrity and the measurement of the resistance of shielding wires by the current of 10[A]
-
Measurement BONDS general and selective type parameters
-
Measurement of circuit impedance “phase- phase” and “phase - neutral particle” and the calculation of the expected current [KZ].
-
Measurement of the insulation resistance, grounding, specific conductivity of ground, integrity of ground wires
-
Measurement of the currents of leakage (with the option [NT]96U)
-
Measurement of current and voltage (True RMS), frequency, power - active, reactive, complete - and capacity rate
-
Measurement of energy - active and reactive
-
Determination of the order of the alternation of the phases
-
Measurement and the registration of the pulses of overvoltage, dips, deviation of frequency, short-term overvoltage
-
Measurement of the harmonics of current and voltage (to 49 harmonics inclusively)
-
Measurement and the registration of temperature, humidity, illumination, level of noise, of sound pressure (option)
-
Retention of the parameters of 63 tests in the course of 1 months. Memory of 2[Mb]
-
Built-in interface RS232 and powerful [po]
Specification
Only for GSC57 Measurement of the integrity of the ground wires of the med. establishments
|
Measurement of electrical conductivity (integrity) of shielding wires (regime Of auto, TRimer+, RTimer-) |
|
Range, W |
Permission, W |
Accuracy |
|
0,01 - 9,99 |
0,01 |
± 2%[IV] + of 2 unit of mf |
|
10,0 - 99,9 |
0,1 |
|
Poppy is the stress of the test of 4[V] of ≤ V0 of ≤ of 24[V] Test current to 200 mA constant with R of ≤ 13W, permission 1 mA |
|
Measurement of insulation resistance |
|
Test stress, before |
Range, [M]W |
Permission, [M]W |
Accuracy |
|
50 |
0,01 - 9,99 |
0,01 |
±2%[IV] of +2 unit of mf, V/R>1mA |
|
10,0 - 49,9 |
0,1 |
|
50,0 - 99,9 |
0,1 |
±5%[IV] of +2 unit of mf, V/R≤1mA |
|
100 |
0,01 - 9,99 |
0,01 |
±2%[IV] of +2 unit of mf, V/R>1mA |
|
10,0 - 49,9 |
0,1 |
|
100,0 - 199,9 |
0,1 |
±5%[IV] of +2 unit of mf, V/R≤1mA |
|
250 |
0,01 - 9,99 |
0,01 |
±2%[IV] of +2 unit of mf, V/R>1mA |
|
10,0 - 49,9 |
0,1 |
|
200,0 - 249,0 |
1 |
|
250 - 499 |
1 |
±5%[IV] of +2 unit of mf, V/R≤1mA |
|
500 |
0,01 - 9,99 |
0,01 |
±2%[IV] of +2 unit of mf, V/R>1mA |
|
10,0 - 49,9 |
0,1 |
|
200,0 - 499,0 |
1 |
|
500 - 999 |
1 |
±5%[IV] of +2 unit of mf, V/R≤ of 1mA |
|
1000 |
0,01 - 9,99 |
0,01 |
±2%[IV] of +2 unit of mf, V/R>1mA |
|
10,0 - 49,9 |
0,1 |
|
200,0 - 999,0 |
1 |
|
1000 - 1999 |
1 |
±5%[IV] of +2 unit of mf, V/R≤1mA |
|
Max test stress 1,3 * the rating Current [KZ] < of 6.0 mA with 500 [v] Rating of the test current > of 2,17 mA with 500[V] and 230[k]W of load and >1[mA] with the remaining conditions |
|
Checking the tripping time OF THE BONDS |
|
Test current 10/30100/300/500 mA Type is BONDS ACE, A general and selective Stress is phase/earth 100 - 255[V], 50 Hz |
|
Range, ms |
Permission, ms |
Accuracy |
|
½ I∆N, I∆N 0 - 999 2I∆N is 0 - is 200 is general 0 - 250 selective 5I∆N BONDS 0 - 50 general 0 - 160 selective |
1 |
±2%[IV] of +2 unit of mf |
|
Contact voltage Of u[p] |
|
Stress, before |
Permission, before |
Accuracy |
|
0 - 2 * U[p] (Of u[p] from 25 [v] to 50 c) |
0,1 |
-0%, + 2%[IV] of +2 unit of mf |
|
Measurement of the impedance of grounding without turning off OF THE BONDS |
|
Range, W |
Permission, W |
Accuracy I∆N |
|
1 1999 |
1 |
-0%, + 5%[IV] of +2 unit of mf |
|
Test current 0,5 IDN for the test Of u[p], 15[mA] for Ra of 15[mA] test |
|
Checking the differential current of turning off OF THE BONDS |
|
Type OF THE BONDS |
Range I∆N, mA |
Permission, mA |
Accuracy I∆N |
|
With I∆N of ≤ 10 mA |
|
ACE |
(0,5 - 1,4) *I |
0,1*I |
-0%, + 5% OF I∆N |
|
A |
(0,5 - 2,4) *I |
0,1*I |
-0%, + 5% OF I∆N |
|
With I∆N of >10 mA |
|
|
|
|
ACE |
(0,5 - 1,4) *I |
0,1*I |
-0%, + 5% OF I∆N |
|
A |
(0,5 - 2)*I |
0,1*I |
-0%, + 5% OF I∆N |
|
Frequency (current loop and measurement BY BONDS actively only with 50[Gts]) |
|
Range, Hz |
Permission, Hz |
Accuracy |
|
47,0 - 63,6 |
0,1 |
±1%[IV] of +1 unit of mf |
|
Stress |
|
Range, before |
Permission |
Accuracy |
|
0 - 460 |
1 |
±3% of IV of +2 unit of mf |
|
Measurement of the resistance of chain (phase- phase, phase - neutral particle) |
|
Range, W |
Permission, W |
Accuracy |
|
0,01 - 19,99 |
0,01 |
±5% of IV of +3 unit of mf |
|
20,0 - 199,9 |
0,1 |
|
Max. current spikes with the test stress: 100[V] of 3,17[A] 230[V] of 6,64[A] 400[V] of 11,5[A] test stress phase- neutral particle/phase - phase 100 - 255[V] with 50[Gts] |
|
The measurement of the resistance of tire (phase - earth) |
|
Range, W |
Permission, W |
Accuracy |
|
0,01 - 19,99 |
0,01 |
±5% of IV of +2 unit of mf |
|
20,0 - 199,9 |
0,1 |
|
200 - 1999 |
1 |
|
Max. current spikes with the test stress: 100[V] of 3,17[A] 230[V] of 6,64[A] test stress phase- earth 100 - 255[V]/100 - 440[V] with 50[Gts] |
|
The measurement of the resistance of tire without turning off BONDS (phase - earth) Ra of 15[mA] |
|
Range, W |
Permission, W |
Accuracy |
|
1 1999 |
1 |
±5% of IV of +3 unit of mf |
|
Test current 15 mA test stress phase- earth 100 - 255[V] with 50[Gts] |
|
Measurement of the ground resistance with the add. by the pintles |
|
Range, RE W |
Permission, W |
Accuracy |
|
0,01 - 19,99 |
0,01 |
±5% of IV of +3 unit of mf |
|
20,0 - 199,9 |
0,1 |
|
200 - 1999 |
1 |
|
Test current of <10mA - 77.5 Hz Stress out of 20[V] RMS |
|
Measurement of the specific conductivity of ground R |
|
Range, R* |
Permission |
Accuracy |
|
0,60 - 19,99W[m] |
0,01 W[m] |
±5% of IV of +3 unit of mf |
|
20,0 - 199,9 W[m] |
0,1 W[m] |
|
200 - 1999 W[m] |
1 W[m] |
|
2,00 - 99,99 [k]W[m] |
0,01 [k]W[m] |
|
100,0 - 125,5 [k]W[m] |
0,1 [k]W[m] |
|
Measuring circuit is 4 is wire, the carrying of pintles 10 m. test current/stress out of 10[mA]-77,5 [Gts]/[do] of 20[V] RMS |
|
Regime of measurement and analysis of the quality of electric power one and the three-phase networks |
|
Measurement of stress - True RMS |
|
Range, before |
Permission, before |
Accuracy |
The input impedance |
|
15- 310 |
0.2 |
±0,5%[IV] of +2 unit of mf |
300 [k]W (phase - neutral particle) |
|
310 - 600 |
0,4 |
300 [k]W (phase - phase) |
|
Dips and the overvoltage |
|
Range, before |
Permission, before |
Permission, the time |
Accuracy |
Accuracy OTN of 50 Hz (time) |
The input impedance |
|
15-310 |
0.2 |
½ the period |
±1,0%[IV]+2 of unit of mf |
± 10 ms |
300 [k]W (phase - neutral particle) |
|
30-600 |
0,4 |
10 ms |
300 [k]W (phase - phase) |
|
Measurement of current (with the external tongs) |
|
Range * |
Permission, mV |
Accuracy |
The input impedance |
Overload protection |
|
0,005 - 0,26[V] |
0,1 |
±0,5%[IV] of +2 unit of mf |
200[k]W |
5[V] |
|
0,256 - 1[V] |
0,4 |
* if the range of tongs of 1000[V]/1[V], then tester will measure the current of more than 5[A]
|
Power measurement one and the three-phase networks |
|
Type of the measurements |
Range |
Accuracy |
Permission |
|
Active |
0 - 999,9 W 1 999,9 kW 1 999,9 MW 1000 - 9999 MW |
± 1%[IV] + of 2 unit of mf |
0,1 W 0,1 kW 0,1 MW 1 MW |
|
Reactive |
0 - 999,9 VAR 1 999,9 kilovars 1 999,9 Mvar 1000 - 9999 Mvar |
0,1 WHITE RESISTS 0,1 kilovars 0,1 Mvar 1 Mvar |
|
Complete |
0 - 999,9 VA 1 999,9 kVA 1 999,9 mVA 1000 - 9999 mVA |
0,1 VA 0,1 kVA 0,1 mVA 1 mVA |
|
The active energy |
0 - 999,9 VAR 1 999,9 kilovars 1 999,9 Mvar 1000 - 9999 Mvar |
0,1 Wh 0,1 [kVtch] 0,1 [MVtch] 1 [MVtch] |
|
Reactive energy |
0 - 999,9 [VARch] 1 999,9 [kVARch] 1 999,9 [MVARch] 1000 - 9999 [MVARch] |
0,1 [VARch] 0,1 [kVARch] 0,1 [MVARch] 1 [MVARch] |
|
Cos j the measurement of capacity rate |
|
Cos j |
Permission |
Accuracy, expressed before ° |
|
0,20 |
0,01 |
0,6 |
|
0,50 |
0,7 |
|
0,80 |
1,0 |
|
Harmonics - stress and the current |
|
Range |
Base accuracy |
Maximum permission |
|
DC - 25H |
± 5% + of 2 unit of mf |
0,1[V]/of 0,1[A] |
|
26H - 33H |
± 10% + of 2 unit of mf |
|
34H - 49H |
± 15% + of 2 unit of mf |
|
Measurement of environmental parameters |
|
Range |
Accuracy |
Permission |
|
Temperature -20… +80°[S] |
±2%[IV] + of 2 unit of mf |
0,1°[S] |
|
Humidity 0 - 100% OF UR |
0.1%UR |
|
Illumination of 0,001[lks] - 20,00 [lks] 0,1[lks] - 2000 [lks] 1[lks] - 20 000 [lks] |
0.001 - 0,02 [lks] 0,1 - 2 [lks] 1 20 [lks] |
|
Measurement of the leakage current |
|
Range |
Permission |
the accuracy |
[Vkh].[impedans] |
Protection on the overload |
|
0,5 - 999,9 mA |
0,1 mA |
±5%[IV] + of 4 unit of mf |
200[k]W |
5[A] |
General given:
Display of 128x128 with the illumination, the size of the screen of 73x73 mm. Internal storage of 999 tests. The operating temperature of 0… 40°[S], humidity not are more than 80%. Nourishment 1,5 [v] by x of 6 small batteries type LR6 - AA or the net adapter Of [a]050. Overall sizes/mass of 225x165x105/of 1,2 kg. Record of results phase and a potential difference. Current of phase, the current of neutral particle. Power - active, reactive, complete. Active and reactive energies. Harmonics to 49 - GO of order.
Delivery set:
- instrument,
- KITGSC5 - collection of 4 wires (2 m) with 4 clamps of the type “crocodile” and 2 test wires
- HTFLEX33 - flexible current tongs 3 pcs 300 - 3000 A
- HW1254 - case
- [S]2033 - 3 wire cable Of shuko
- KITTERRNE - case with 4 wires and 4 metals. by the pintles
- C2001 - cable for the connection for the sake of the computer and ON TOPLINK 2000
- A0050 - net adapter
- Management of user down the instrument and the management on [po]
- Certificate of calibration according to ISO9000
Options:
- adapter for measuring the impedance with the high resolution - IMP57
- sensor for the level measurement of noise and sound pressure - [NT]55
- sensor for measuring of temperature and humidity - [NT]52/05
- sensor for measuring the illumination - [NT]53/05
- shoulder strap for the carrying-over - CN0050
- 4 wires 5 m with “the crocodiles” for the test of electrical conductivity (10[A])
- 4 wires 10 m with “the crocodiles” for the test of electrical conductivity (10[A])
- tongs for measuring the currents of leakage - [NT]96U
- current tongs 200 - 2000 A, ACE - [NR]30[S]2
- current tongs 3000 A, ACE - [NR]30[S]3
- current tongs 1 100 - 1000 A [N]T96U
Current page:
Complex multifunctional testers GSC53 and GSC57 |