Instrument makes it possible to analyze all parameters of electric power according to ALL-UNION STATE STAN. 13109-97 with the high accuracy and the wide range of the measured values: - The variation of the stress - The fluctuation of the stress - The dose of the flicker: short-term, prolonged - The nonsinusoidality: curve of stress, harmonic components of the three-phase networks - The frequency deviation - The pulse overvoltage - The duration of dip - The asymmetry of the voltage of the three-phase networks - The coefficient of the temporary overvoltage 
Instrument includes the functions:
1. Analyzer of the quality of the electric power 2. Oscillograph 3. Multimeter 4. Registrar
- The presence of the function Of true RMS makes it possible to conduct the measurements of the full values of voltage and current with the high accuracy.
- Measurement of the harmonics of current and voltage to 50, the parameters OF BONDS.
- Image of waveform both before the digital and before the graphic form
- 4 channels for measuring of current and 4 channels for measuring the stress
- It works with single-phase networks 2 and 3 wire diagrams, by three-phase networks 3 and 4 wire diagrams.
- Measurement of current with the use of any of five types of current-measuring tongs - 5/100/500/1000/5000 A
- Simultaneous measurement and retention of results makes it possible not to lose valuable information, especially about the failure. Ranges of record from 1 s. to 2 hours (time interval between two sequential [vyborkami])
- Colored [ZHKD] 6,4”, 640*480 of the pixels
- Compact and light instrument: with size the sheet of the paper of the size Of [a]4 and with the weight of 2,25 kgf
- Possibility of conducting the continuous measurements in the course of one month
- Large storage capacity for record and storing the data: internal storage to 13 mb., the additional maps of memory to 512 mb.
- Built-in disk drive for PCMCIA of maps (map of memory)
- Built-in interfaces RS232 LAN- port for the work through the Internet, the connection for the sake of PK and the printout of the results
- Channels of the entrance/of output for the warning system
- Input resistance: on the stress: 4 [M]W ±10%, on the current: 200 [k]W ± 10%
- Conclusion of measured data before the real time: the waveform, vectors, measured values and harmonics.
- Maximum stress: 780 [v] ACE, 1103 [v] peak, the current of 1,7[V] ACE, 2,4 [v] the peak
Specification
Instrument conducts measurement and analysis not only of the parameters of the indicated beside ALL-UNION STATE STAN. 13109-97, but also following values
|
Stress RMS |
To 600 [v], the accuracy is THE ACE: ± 0,2% OF IV + 0,1% OF [VPI], DC: ± 0,3 % ИВ+0,4 % ВПИ |
|
Current RMS |
To 5000 A, depending on tongs, the accuracy: ± 0,2% of IV + 0,1% OF [VPI] + the accuracy of the tongs |
|
Overvoltage (pulses) |
2 MHz frequency, 2000 [v] peak, the conclusion of signal 4 ms., min. the determined duration of 5 m[sek]., the accuracy: ± 5,0% OF IV ± 20 [V] |
|
Frequency |
42,500 - 69,000 Hz, the accuracy: ±10 MHz (10-100% of range) |
|
Voltage surges |
Amplitude and duration of jump is measured. Accuracy is the same as in stress RMS |
|
Dips |
Amplitude and duration of failure is measured. Accuracy is the same as in stress RMS |
|
Active power |
Is calculated continuously every 10-12 cycles, accuracy ± 0,2% OF [IV]+ 0,1% OF [VPI]+ the accuracy of the tongs |
|
The reactive power |
Accuracy: ± 1[ed]. mf. from the calculation of each measured value |
|
Capacity rate |
Range from 1,000 - 0,000 and to + 1,000; the accuracy ± of 1 un. of mf. |
|
Shift coeff. of the power |
It is calculated as a phase difference of the fundamental harmonics of voltage and current.
Range: From -1,000 to 0,000 and to +1,000; the accuracy ± of 1 un. of mf. |
|
Coeff. imbalance. the stress |
It is calculated for 3 phase networks of 3 wire and 4 wire diagrams |
|
Coeff. imbalance. the current |
It is calculated for 3 phase networks of 3 wire and 4 wire diagrams |
|
Twinkling DV10 |
Short period of the twinkling Of pst, the long period of the twinkling Of plt. DV10, DU, accuracy ±2%[IV] |
|
Twinkling IEC |
Standard IEC61000-4-15. the accuracy ± 5% of IV |
|
Harmonics |
Stresses, current, the power: with the 1-[oy] to the 50-[oy] |
|
Accuracy |
Stress, the current: 1-20: ± 0,5% OF IV + 0,2% OF [VPI]; 21-50: ± 1,0% OF [IV]+ 0,3% OF [VPI] the power: 1-20: ± 0,5% OF IV + 0,2% OF [VPI]; 21-30: ± 1,0% OF IV + 0,3% OF [VPI]; 31-40: ± 2% OF IV + 0,3% OF [VPI]; 41-50: ± 3% of IV |
Options
| the current tongs |
9694 |
9660 |
9661 |
9669 |
9667 |
| Current, THE ACE |
5[A] |
100[A] |
500[A] |
1000[A] |
500[A], 5000[A] |
| Stress |
10[mV]/[A] |
1 [mV]/[A] |
1 [mV]/[A] |
0,5 [mV]/[A] |
5000[mV]/[A] |
Accuracy Amplitude Phase |
±0,3%[IV]±0,02% OF [VPI] ±2° or is less |
±0,3%[IV]±0,02%[VPI] ±1° or is less |
±0,3%[IV]±0,01%[VPI] ±0,5° or is less |
±1,0%[IV]±0,01%[VPI] ±1° or is less |
±2%[IV]±1,5 of mV ±1° or is less |
| Frequency |
±1,0% or it is less than 66[Gts] - 5[kGts] |
±2,0% or < 66[Gts]-5[kGts] |
±1%BD±1.5[mV] |
| Ø[zakhvata] |
Ø15 mm |
Ø15 mm |
Ø46 mm |
Ø55 mm |
Ø254 mm |
| Overall sizes of/[massa] |
46*135*21 mm 230 deg |
46*135*21 mm 230 deg |
77-151*42 mm 360 deg |
99,5*188*42 mm 490 deg |
57*86*30 mm, 140 deg |
General given Max. stress 780 [v] ACE, 1103 [v] peak, the current of 1,7[V] ACE, 2,4 [v] the peak The operating temperature of 0… 40 °[S], humidity not are more than 80% Overall sizes/mass Of [a]4/of 2,25 kgf
It enters into delivery set 3196 - analyzer, wire with the clamps for measuring the stress 3 m, the unit of storage batteries, net of [adapter]/[ZU], LAN joint, the management of the user
Current page:
Analyzer of the quality of electric power 3196 |